OT Air Conditioning & Laminar Air Flow System (HEPA)

Modular Operation Theatre

Manufactured by S.S. Engineering Enterprises

Product description

A dedicated air-handling unit for the operation theatre, with HEPA-filtered air flowing down over the operating table, positive pressure and controlled temperature and humidity. It is designed around the air-conditioning guidelines that NABH published for operation theatres in 2018.
Key features
  • A dedicated air-handling unit for each OT, not shared with other areas
  • Terminal HEPA filters in the ceiling above the operating table
  • Unidirectional, downward air flow from a non-aspirating laminar diffuser
  • Positive pressure kept in the OT at all times, including when it is not in use
  • Temperature and humidity monitoring and display
  • Filters reachable for service; testing and recording of air changes, particle count, air velocity, pressure and HEPA integrity
  • NABH advises against window or split air conditioners in operation theatres

Product specifications

Typical values. The exact rating is confirmed for each project at quotation.
  • Air changes: At least 20 per hour in total, of which at least 4 fresh air
  • Air velocity: 25 to 35 ft/min (about 0.13 to 0.18 m/s) at the diffuser face
  • Room pressure: At least 2.5 Pa above the adjoining areas
  • HEPA filtration: 99.97% at 0.3 µm or better, covering one foot beyond the table on every side
  • Supply air cleanliness (at rest): ISO Class 5 for Type A operation theatres, ISO Class 6 for Type B
  • Temperature and humidity: 21 ± 3 °C (18 ± 2 °C for joint replacement) and 20 to 60% relative humidity
  • Validation: NABH recommends every 6 months